导航
产品搜索
首页 / 程序控制器 / 德国西门子燃烧器程控器 LFL1.322
程序控制器
德国西门子燃烧器程控器 LFL1.322
Basic parameters
功能特点
Functional features

LFL1...系列燃气燃烧器控制器  

  品牌:SIEMENS(西门子)  

 

  产地:德国  

 
  产品介绍  
                         
 

  The burner controls of the LFL1... range are designed for the control and supervision of forced draught gas burners of both expanding flame and interrupted pilot construction of medium to high capacity. They are universally applicable and can be used for both multistage and modulating burners as well as for dual-fuel burners and for burners of stationary air heaters (WLE to DIN 4794). 

 

  The difference between series 01 and 02 lies in the duration of the safety time for the pilot burner of burners using pilot gas valves. 

 

  For 

 atmospheric burners of high capacity,type LFL1.638 is available.  

  For burner controls used with burners in continuous operation, 

 types LGK16... .  
  型号表  
                   
                                                                                                                                                                                                                                                                                                                                                                                                                                         
    LFL1.122 Series 02     LFL1.133 Series 02     LFL1.322 Series 02     LFL1.333 Series 02     LFL1.335 Series 01     LFL1.622 Series 02     LFL1.635 Series 01    LFL1.638 Series 01 
  t1     10     9     36     31.5     37.5     66     67.5    67.5 
  t2     2     3     2     3     2.5     2     2.5   2.5 
  t2’     -     3     -     -     5     -     5    5 
  t3     4     3     4     6     5     4     5    5 
  t3’     -     -     -     -     2.5     -     2.5   2.5 
  t4     6     6     10     12     12.5     10     12.5    12.5 
  t4’     -     -     -     -     15     -     15    15 
  t5     4     3     10     12     12.5     10     12.5    12.5 
  t6     10     14.5     12     18     15     12     15    15 
  t7     2     3     2     3     2.5     2     2.5   2.5 
  t8     30     29     60     72     78     96     105   105 
  t9     2     3     2     3     5     2     5    7.5 
  t10     6     6     8     12     10     8     10    10 
  t11     optional     optional     optional     optional     optional     optional     optional   optional 
  t12     optional     optional     optional     optional     optional     optional     optional   optional 
  t16     4     3     4     6     5     4     5    5 
  t13     10     14.5     12     18     15     12     15    15 
  t20     32     60     -     27     22.5     -     -    - 
 
                                                                                                                   
  t1     预吹扫时间,风门打开     t7     从开始到端口7开始工作的间隔时间(风机2开始延迟时间)  
  t2     安全时间     t8     启动持续时间(没有端口11和12)  
  t2’     安全时间或1段火安全时间     t9     第二安全时间  
  t3     预点火时间,短(点火变压器连接端口16)     t10     从启动到空气压力监测开始的间隔时间(不包括风门运行时间)  
  t3’     预点火时间,长(点火变压器连接端口15)     t11     风门打开到最大位的运行时间  
  t4     从t2开始到端口19打开2段火的间隔时间     t12     风门运行到小火位的时间  
  t4’     从t2’开始到端口19打开2段火的间隔时间     t13     允许的燃烧后时间  
  t5     从t4结束到端口20打开比例控制或阀门的间隔时间     t16     直到风门给出打开命令的间隔时间  
  t6     后吹扫时间(带风机2)     t20     程控器锁定后的顺序自检时间